**Connector pinout**

|  |  |  |  |
| --- | --- | --- | --- |
| 2-pin 3.5 mm | Pin | Signal | Description |
| ![image](media://6248122b-5f0c-40f1-b77d-72593662c505) | S | Signal | Versatile port signal (input/output) |
| G | GND | Ground |

> Macro (excerpt)
> 
> |  |  |  |  |
> | --- | --- | --- | --- |
> | 7-pin 3.5 mm | Pin | Signal | Description |
> | ![image](media://080b5c7b-624d-474a-89f0-9918efcb369c) | S1 - S6 | Signal | Versatile port signal (input/output) |
> | G | GND | Ground |

Depending on the application, the **versatile port** can be used in the following multiple ways:

> Macro (toc)

> ⚠️ Warnings
> ⚠️ 
> ⚠️ - The port is protected to a **maximum of 30 VDC**. Exceeding this voltage may damage the port.
> ⚠️ - Incorrect wiring may damage the versatile port or the connected device.
> ⚠️ - All versatile ports in the unit have a common ground that is connected to the grounds of other control ports. That means versatile ports are not isolated from other control ports.

The following picture describes the connection of a versatile port for analog input and digital output usage.

![image](media://11d228e3-eee6-4f71-8d1d-b6e37c1cd4d7)

# Digital input

The voltage input can sense digital signals from contact closures, switches, relays, logic level signals from motion detectors, partition sensors, alarm panels, triggers, energy meters, etc.).

> ℹ️ For digital input using the output has to be in an open state and current pull-up and current pull-down can be used.

**Parameters **of digital input:

- Input protected to 30 VDC / -12 VDC
- Input impedance >100 kΩ
- Adjustable digital filter
- Adjustable threshold

**Examples of use:**

| **Connection** | **Usage** |
| --- | --- |
| ![image](media://8c2975a6-5e4c-4387-907b-e23f2ae96b27) | Detecting a pushbutton or contact closure. |

# Digital pulse counter

This mode allows for the measurement of transitions from an inactive to an active level on a channel.

**Parameters **of digital pulse counter:

- Adjustable threshold and input impedance as f
- Pulse length min. 1 ms, max. frequency 500 Hz
- Max. number of pulses 2 147 483 647 (Long)
- Adjustable digital filter

**Examples of use:**

| **Connection** | **Usage** |
| --- | --- |
| ![image](media://9c785b83-d57e-4219-9cac-84aa656d8464) | Energy meters S0 interface pulse counter from third-party energy meters. S0 interface defines a simple galvanically isolated open-collector output channel. |

# Voltage input

The voltage input can sense analog signals from the DC voltage level or changes in resistance from volume control potentiometers, temperature and light sensors, water level meters, etc.

> ℹ️ For voltage input usage the output has to be in an open state.

**Parameters **of voltage input are as follows:

- Protected to 30 VDC maximum
- Range 0 ÷ 2.5 VDC, 0 ÷ 10 VDC, auto
- Input impedance >100 kΩ
- Resolution 10-bit
- Adjustable digital filter
- Accuracy ±1 % of range (digital filter applied)

**Examples of use:**

| **Connection** | **Usage** |
| --- | --- |
| ![image](media://03a12f07-c16d-4c4a-aa56-0910b5fdabf6) | Detecting a voltage from sensors with voltage output 0 - 10 VDC. |
| ![image](media://9d133f4f-ea07-48b9-8e86-954b25b85ae1) | Reading voltage on potentiometer with external power supply |

# Resistance input

The resistance input can measure resistance e.g. from a room potentiometer for light, temperature, and volume control.

**Parameters **of resistance input are as follows:

- Range 2 kΩ , 20 kΩ , 200 kΩ , auto
- Resolution 10-bit
- Adjustable digital filter
- Accuracy (digital filter applied)
  - 100 Ω ÷ 800 Ω: ±3 % of reading, ±0.1 % of range
  - 800 Ω  ÷ 20 kΩ: ±0.3 % of reading, ±0.1 % of range
  - 20 kΩ  ÷ 200 kΩ: ±1 % of reading, ±0.1 % of range

**Examples of use:**

| **Connection** | **Usage** |
| --- | --- |
| ![image](media://a71aa853-c0e9-4b18-a848-c6d33f6d1a0f) | Reading resistance e.g. from room potentiometer for light, temperature, and volume control. |

# Digital output

The digital output provides an on/off closure signal for driving a relay and trigger inputs from a variety of devices. For digital output, the **open collector** switch is used and the pull-up or pull-down current-source can be used. 

**Parameters** of digital output are as follows:

- Open collector
- Max. sink current 200 mA / max. 30 VDC
- Catch diodes for use with inductive load
- Current-source pull-up 9 mA (max. 10 V)
- Current-source pull-down -9 mA (max. -10 V)

**Examples of use**:

| **Connection** | **Usage** |
| --- | --- |
| ![image](media://67963e18-6256-4da3-8f3d-599b79cfb212) | Driving relays with low-voltage coil |
| ![image](media://51d55e8e-efab-434d-9810-2d901fe30970) | Driving LEDs for custom indicators on keyboards, control panels, etc. |
| ![image](media://5909a4cd-0b02-4e77-b39b-0209857ba4ea) | Driving LED strips with max. voltage 30 VDC and max. current 200 mA. |

# IR output

This mode provides output for infra-red emitters IR Adapter. 

**Parameters **of IR output are as follows:

- Maximum IR carrier frequency 500 kHz
- Up to **3** original infra-red emitters IR Adapter /I can be connected to each output in parallel. All emitters send the same IR codes. This configuration can be used for different types of devices.

> ⚠️ It is **not recommended** to connect more infra-red emitters of various manufacturers in parallel because the output can be either overloaded or damaged.

 **Example of use:**

![image](media://a9b0ebb7-4aa7-4487-9128-6c4734b813ef)

# Serial output

This mode provides a one-way RS-232 output channel. 

**Parameters **of serial output are as follows:

- RS-232
- Output signal level range is -12 V to +12 V
- Serial data baud rate 300 Bd ÷ 115 200 Bd (bps)

**Example of use:**