Depending on the type of wall, the following installation methods can be used:

> Macro (toc)

# Using Adhesive Foil

Installation using adhesive foil is typically used for a **glass wall** installation. Delivered adhesive foil is installed on the wall and then the touch panel is attached by adhesive tape installed on the rear side of the back cover.

> ⚠️ The adhesive foil not only has an aesthetic purpose, so that the back of the panel is not visible behind the glass, but also significantly increases the bonding strength of the panel. **Therefore, the use of adhesive foil is mandatory.**

|  |  |
| --- | --- |
| ![image](media://42e427e2-2e0d-4af7-8e1d-82f26e33c907) | **Degrease **(typically glass) surface with alcohol and let it dry.<br>**Mark the top of the foil** at such a height that the centre of the panel is at the recommended height of 1500 mm from the floor. |
| ![image](media://47da550d-126a-430c-906c-ba3ce92721c1) | **Partly remove** protective film from adhesive foil and cut it. |
| ![image](media://bd9f37e2-7197-4c8d-a9ab-1f2e5faf8453) | Use vertical ruler or level to **adjust correct foil vertical position**. Put foil on the wall with the protective film (not with adhesive part) to the ruler or level. |
| ![image](media://66489d57-b1af-4b29-af95-bbac584a95be) | **Stick the adhesive part** of foil using delivered squeegee. |
| ![image](media://179155c3-8b52-4508-99f3-1f1b560abb69) | **Partially remove** the protective film and stick the rest of the foil using a squeegee. |
| ![image](media://43bade0c-c067-44a5-8dc2-846f8910f13e) | **Squeegee** lengthwise from the center outwards with overlapping strokes. |
| ![image](media://6a6a2610-b43b-45ab-8280-1ceae631ea3d) | **Loosen the fixing screw** using delivered Allen key - **1** and remove back cover of the panel - **2** , **3** . |
| ![image](media://617ea3bb-a0bc-42e5-8c30-e00a456e928e) | **Position **of back cover must be oriented as  
displayed above - cable bushings are left, right and bellow side oriented. |
| ![image](media://f854abab-cb08-42ed-8354-e0ca68e08004) | **Degrease **the back of the panel and attach two double-sided adhesive strips to the back of the panel. The strips should be located along the top and bottom edge of the back panel. |
| ![image](media://f9aa734d-253a-476d-903b-74300f110a4a) | **Degrease **foil installed on the wall and left it  
completely dry. Remove protective film from the adhesive tape (installed on the rear side of the back cover) and carefully attach it on the foil installed on the wall.<br>> ⚠️ **It is recommended to wait at least 24 hours, but preferably 72 hours, before proceeding to the next step (installation of the panel itself) to achieve maximum bond strength**. |
| > ℹ️ After applying the **adhesive tape**, the bond strength will increase as the adhesive spreads across the surface (also known as “wet-out”). 
> ℹ️ 
> ℹ️ - **At room temperature**:
> ℹ️   - **50%** **of the ultimate bond strength will be achieved after 20 minutes, **
> ℹ️   - **90% after 24 hours, **
> ℹ️   - **100% after 72 hours. **
> ℹ️ - This process occurs more **quickly at higher temperatures** and **more slowly at lower temperatures**.
> ℹ️ - **Ultimate bond strength can be achieved more quickly** (and in some cases, bond strength can be increased) **by exposing the bond to elevated temperatures** (e.g., 66°C [150°F] for 1 hour). This can improve adhesive wetting on the substrates.
> ℹ️ - Abrading the surfaces or using primers/adhesion promoters can also increase bond strength and help achieve ultimate bond strength more quickly. |
| ![image](media://8f134e89-3603-4966-a4c4-b151345c5934) | **Install cable** to the selected bushing and install appropriate cable cover. Cable length inside is 25 cm. Covers for flat and round cables as well as for unused bushings are delivered. Covers are fixed with adhesive tape. |
| ![image](media://2710e044-db90-440d-926a-bd275ddd5971) | **Connect Ethernet cable** to the panel and put  
the panel on the back cover - **1** , **2** . Carefully  
tighten the fixing screw to fix panel on the back cover - **3**. |

# Using Screws

Installation using screws can be used for **dry walls**, wooden walls, and furniture as well as for holders compatible with **VESA standard** 75 mm x 75 mm. Four holes are prepared on the rear side of the back cover.

|  |  |
| --- | --- |
| ![pic1.png](media://07dbb9db-987e-4629-9727-37baca802f5d) | **Loosen **the fixing screw using delivered Allen key and remove back cover of the panel. |
| ![pic2.png](media://ea995cfb-cb29-4644-a791-31aee4049a6b)<br>![pic2_B.png](media://28808cf1-efcf-45f0-ad41-79b54aced5de)<br>![pic2_A.png](media://effe914c-6040-4d85-ba61-16cd9571f059) | Install the cable so that it passes through one of the holes in the back cover or a side cable bushings and put back cover on the wall.<br>Recommended cable length from the wall is 250 mm. Recommended height from floor to center of the panel is 1 500 mm. |
| ![pic5.png](media://e4401e34-5efb-4997-bd73-26d854bb71aa) | Cover unused side openings with the enclosed covers. |
| ![pic6.png](media://759599bd-3f2f-4e1d-a1f0-b33e731af4ed) | **Fix cover** on the wall using appropriate screws depending on the wall material. |
| ![pic7a.png](media://020860dc-168e-4393-aa59-0e5f54d58839) | **Connect Ethernet cable** to the panel |
| ![pic8.png](media://c3607b1f-436d-4da1-bcba-496cf11a47b9) | Put the panel on the back cover.<br>Carefully tighten the fixing screw to fix panel on the back |